as soon as I plug-in a standard heating pad or a hair dryer into any kind of bedroom duplex, the lights dim; and/or trips the circuit breaker. The house is of brand-new construction-- placed in organization 31 Dec 2013. My question is: have the right to I safely change the present 15 AMP Breaker v that that a 20 AMP? . . . The company cable is that 14 Gauge Copper Conductor.


*

*

No!

The just safe method to increase the circuit"s capacity is by replacing the cable with among adequate gauge. For 20 amps, 12 AWG copper is enough for increase to about 100 feet.

You are watching: Upgrading circuit breaker from 15 to 20 amp

If you just replace the breaker, the wire deserve to overheat and also ignite the structure from inside the walls.

To deal with the dimming issue, examine that the outlet is in great condition and also that the wires are securely fastened and not showing any signs of overheating: blackening or ns of the copper shininess. Also, check the end of the wire within the business panel, both neutral and also "hot" (black) wire. If those are okay, set the appliances to a lower wattage setup or replace them with reduced wattage models.


share
improve this price
monitor
edited Dec 20 "13 at 20:23
answer Dec 11 "13 at 0:14
*

wallykwallyk
12k11 gold badge2020 silver- badges4949 bronze badges
1
include a comment |
4
Absolutely NOT.

National Fire Protection firm (NFPA) typical Number 70, National electrical Code (NEC), adopted by most states (exceptions room Missouri, Mississippi and also Arizona), needs the branch circuit Over existing Protection an equipment (OCPD --typically a circuit breaker (CB) nowadays, quite than a fuse from days that yore) to protect the cable/wiring hidden in your wall surfaces from overheating through de-energizing (shut off/open circuit) all outlets (lighting & receptacles) for the circuit by tripping/blowing.

Lights dimming and CBs popping is a sure sign your home was not built to manage heating blankets and hair dryers in the bedroom. Swapping the end a 20 amp breaker for the 15 amp breaker will certainly violate NEC 210.19(A)(1) and administer cause for your insurance agency not to reimburse your losses from fire & acting damage and also the water damages from the fire department flooding her house.

Wire is made smaller when manufactured by drawing/stretching it. The more times its extended the smaller it gets. This is why American wire Gauge (AWG) appears backwards, i.e. 14AWG has actually a smaller sized diameter 보다 10AWG due to the fact that it was extended more.

15 amp rated circuit breakers usage 14 AWG present carrying conductors (black warm & white neutral) + a green ground cable which normally carries no current in sector standard outer white non-metallic sheathed cable dubbed NM-B 90 degree Centigrade rated "Romex".

20 amp rated circuit breakers use the same configuration however 12 AWG, i beg your pardon is a larger diameter wire than 14 AWG, and therefor has actually less resistance for the exact same distance/footage indigenous the pack center/panelboard circuit breakers. 12 AWG NM-B sheathing is colored yellow.

10 AWG through orange sheathing would certainly be even far better electrically, but much more expensive and not required by "code", the NEC.

Blame every this mumbo jumbo on Physics and also a German called Georg Simon Ohm who produced a law that even Donald J. Trump can"t repeal. Voltage lose (V) = present (i amps) time resistance (r ohms). And Power lose = current squared (i to the twoth power) time resistance (R).

When you draw too much present through a slim wire, because its not a superconductor, you"re converting electric energy into heat energy from Ohm"s resistive loss, resulting in less electric energy (a voltage drop) getting to your fill (appliance, light bulb, stereo, ...). The excess warm in the wire and also inside your wall causes the insulation to fail over time, developing a potential short circuit add by sparks that ignite flammables.

Have a licensed and insured electrician (Journeyman or Master) or electrical contractor include a brand-new 20 amp circuit, or change the existing 14 AWG cabling through 12 AWG cabling, or usage your hair dryer in the bathroom i m sorry should currently have a GFCI per NEC 210.8(A)1) and 20 amp receptacle every NEC 210.11(C)3) set up within 3 feet the the sheet of a container per NEC write-up 200, ar III compelled Outlets, 210.52 apartment Unit Receptacle Outlets, (D) Bathroom.